| Place of Origin: | China |
|---|---|
| Brand Name: | AI |
| Certification: | ISO |
| Model Number: | BDV-II |
| Minimum Order Quantity: | 1 Set Transformer Oil Test Set |
| Price: | Negotiable |
| Packaging Details: | Transformer Oil Test Set packed in Plywood case |
| Delivery Time: | 15 days |
| Payment Terms: | T/T, Western Union, L/C |
| Supply Ability: | 100 sets per month |
| Power Supply: | AC220V±10%, 50Hz/60Hz | Display: | LCD |
|---|---|---|---|
| Test Standard: | IEC 60156/IS6792/BS 5874/ASTM D1866/ASTM D877 | Voltage Output: | AC 0V~100KV |
| Size: | 620 Mm*430mm*330mm | Weight: | 41kg |
| Keyword: | Transformer Oil Tester Set | Rate Of Voltage Rise: | 0.5kv/s±5%, 2kv/s±5%, 3kv/s±5%,5kv/s±5% |
| Highlight: | 100KV Oil Test Set,Insulating Liquid Testing,IEC 60156 |
||
I. Introduction:
BDV-II Transformer Oil Test Set is designed according to the national standard IEC156 Insulation Oil Dielectric Strength Test Method;
This transformer oil tester has large LCD display, micro-printer and can store 100 groups data;
This oil tester kit is multi-functional, stable, and easy for operation;
II. Functions:
Breakdown test of user-defined;
Proof test;
IEC60156/IS6792/BS5874 test;
ASTM D1816 standard test;
ASTM D877 standard test;
5 minutes standard test;
Manual test;
Calibration interface for customers;
This transformer oil tester can upload data to PC and making word report automatically;
Result can be printed by insulation oil tester;
III.Specifications:
| Output voltage | AC 0V~100KV |
| Rate of voltage rise | 0.5kv/s±5%, 2kv/s±5%, 3kv/s±5%,5kv/s±5% |
| Max test times setting for user-defined mode | 9 |
| Stir time setting for user-defined mode | 0~999s |
| Waiting time setting for user-defined mode | 0~999s |
| Test error | 3%RDG+0.3%FS |
| Display | 256´128 LCD |
| Maximum storage capacity | 100 groups of test data |
| Power supply | AC220V±10%, 50Hz/60Hz |
| Working environment | 0-50℃, ≤80%RH |
| Size | 620 mm*430mm*330mm |